Underfloor air-distribution (UFAD) systems have been
used for comfort-conditioning office spaces in United States office buildings
since the early 1990s. Systems were initially employed in high-tech office
spaces where in addition to occupant comfort, ease of office space
re-configuration (churn) was a priority for building owners. UFAD systems
deliver air to occupied spaces through floor-mounted outlets supplied by
conditioned air from a pressurized plenum beneath the suspended floor.
A properly designed UFAD system takes advantage of thermal stratification. The key is to have a diffuser that rapidly mixes air without penetrating the stratification layer at the ceiling. The pressurized plenum -- the area between the slab and raised floor -- is essentially a large duct maintained at a constant pressure differential to the room above; typically between .05 and .10 in. pressure (w.g.). This pressure is maintained through the supply of conditioned air from a number of supply-duct terminations. The spacing and location of these ducts are dependent on the air supply requirement and the plenum depth which typically ranges from 12” to 24”. If zone control is desired from the underfloor plenum, it can be partitioned into separate zones. The return air for a UFAD system should be located at the ceiling or high sidewall. This allows heat from the ceiling light to be returned before it is able to mix with the occupied zone. There is also a small amount of “free cooling” due to the natural buoyancy of hot air.
Some of the concerns typically associated with these
systems are humidity, dirt, spillage, and leakage. A potential problem with the
higher supply temperatures used in access floor air-distribution systems is the
higher potential moisture content of the 60-65˚F supply air most commonly used
in these systems. The supply system must reduce relative humidity to less than
65˚F. Potential solutions are either the reheat or blending of air to achieve a
65˚F supply, 55˚F dew-point condition. System designs utilizing condenser water
reheat, run-around coils (face, bypass), and other strategies can be employed
to solve these potential design problems. Other options include the use of
desiccant dehumidification. Although underfloor air-distribution systems are
not recommended for areas with a high potential for spills such as bathrooms,
cafeterias and laboratories, small spills are not a problem for most
applications. Typical swirl diffusers used within the interior have a dirt/dust
receptacle to catch spills and dirt from normal daily use. The dirt/dust
receptacle has a basin that will hold anywhere from 4-6 fl. oz. of liquid. The
dirt/dust receptacle can easily be removed and cleaned to keep dirt out of the
underfloor plenum. Leakage is typically due to poor sealing or the construction
quality at window/wall locations, stair landings, electrical outlets, etc.
These areas have to sealed and framed so the supply air does not travel up the
wall toward the return air. There can also be leakage between the floor panels
which can be reduced by staggering the carpet tiles over the floor tiles. The
key is to limit the number of penetrations into the raised floor which will
reduce the number of areas that need to be sealed.
Since typical floor plenum pressure is less than .10
in w.g. (25 Pa), energy-efficient low-pressure fans can be used. In place of
complicated and expensive duct systems required to supply air to each
individual air outlet in a ceiling system, UFAD systems deliver air to building
zones using a limited amount of ductwork to create an air highway.
Where a traditional overhead mixed system provides
comfort-conditioned air from the floor to the ceiling, partially mixed systems
like UFAD save energy by providing comfort-conditioning in the lower occupied
spatial zone. They allow the upper zone to stratify.
In the core of the building where loads are relatively
constant, round (swirl) or rectangular outlets are located in the floor near
the occupants. Outlets typically deliver 80-100 cfm (38-48 l/s) of conditioned
air to the space. Some of the units have volume control adjustability by the
occupants to increase individual comfort levels. The round swirl diffusers are
typically available with an occupant adjustable flow regulator that can be
either manually adjustable or by the use of a room sensor that is connected to
an actuator mounted directly on the diffuser. Installation of swirl units has
been made easy by replacing the mounting ring which was previously attached to
the unit beneath the floor tile with spring clips to provide a press fit
directly into the floor tile. A recent ASHRAE research project (RP-1373) has
also provided data to show that when the height of the air plume to a terminal
velocity of 50 fpm (.25 m/s) is limited to 4.5 feet (1.4 m), the air change
effectiveness (ACE) is improved in the breathing zone. This research has now
been recognized by ASHRAE Standard 62.1-2010 with Addenda A in Table 6-2 by
allowing an Ez rating of 1.2 for these conditions. This means that the
ventilation (outdoor) air supplied to the zone can be reduced by 16.7%. For
LEED projects where the credit point for IEQ credit 2 is desired, this 16.7%
can be used in reaching the goal of 30% increased ventilation air.
Some of the biggest challenges for underfloor design
occur on the perimeter of the building where loads are higher and dynamically
changing due to effects of radiation and temperature conduction on the skin of
the building. Where the core of the building is mainly impacted by nearly
constant heat loads, the perimeter system must accommodate swings in heat loads
and heat losses that can occur in a relatively short period of time.
A common method of handling perimeter loads to locate
a fan-powered terminal in the floor plenum near the perimeter. These
fan-powered terminals are ducted to outlets located on the perimeter. A typical
outlet would be a linear bar grille with either a boot plenum or continuously
fed plenum underneath. Equipped with an option hot water or electric heating
coil, the fan unit can deliver warm air in response to a space thermostat.
Unfortunately, as linear grilles get longer, the mass effect of the discharge
air jet projects the air higher than required. If the throw from the outlet is
too long and reaches the ceiling, it may deflect downward into the space and create
unwanted drafts in the interior zones. In some cases, cool air from the floor
plenum is supplied to the perimeter zone through the fan-powered unit.
For LEED projects, the operational cost of energy to
run a fan-powered terminal can be minimized by using ECM fan motors. ECM motors
operate at an efficiency of 70% or greater. The cooler operation of an ECM
motor -- and enhanced construction -- contribute to a longer life and lower
life-cycle cost when compared to standard construction PSC motors. An additional
benefit of an ECM motor is ability to control the fan speed during operation to
provide increased energy savings and better occupant comfort in the occupied
space. ECM motors can also utilize remotely controlled speed controllers (pwm)
that can be controlled through a building management system.
New technology in perimeter systems can lower
installed/operational costs and improve comfort along the perimeter zones. By
installing a continuous bar grille along the perimeter, variable air volume (VAV)
cooling and plenum heating coils can be attached as needed to condition the
perimeter. These cooling and heating units are passive and do not require the
use of a fan terminal. The bar grille can be connected together to provide a
continuous architectural appearance around the perimeter or can be installed in
sections as required for comfort conditioning. The core of the bar grille is
removable from the room to provide access to the unit’s working components.
The VAV-cooling units employ an electrically actuated
sliding damper, which opens and closes a series of transverse apertures to vary
the volume of cool air supplied from the pressurized underfloor plenum into the
space. The sliding damper opens and closes to provide the amount of conditioned
air required to manage the changing conditions as directed by a room thermostat
located in the occupied zone. The transverse apertures manage the supply air to
allow room air to be included into the air pattern. Introducing supply air in
small bundles helps in managing the projection from the outlet and prevents
long throws which create drafts in the occupied space.
The heating plenums also attach to the linear bar
grille. The heating plenums are passive in operation and do not require a
fan-powered terminal to supply air or heat. Located parallel on the perimeter
at the glass, the heating unit mixes the cool convection currents flowing down
the glass with warm-air currents traveling across the floor. These mixed currents
are induced into the inner chamber of the plenum and flow up through the heat
exchanger. The warm current then exit the linear grille at the glass and flow
upward via convection to heat the cool air in front of the glass.
The hydronic heating units have a finned-tube heat
exchanger with heat supplied through a hot-water pipe and controlled by a water
valve to provide the precise amount of heat required to satisfy room
conditions. The electric heating units are of fin-tube construction and have an
SCR control to match the changing heat requirements in the space. The ETL
listed heaters can be found in 120V, 208V, 240V, and 277V supply circuits. The
modular construction of the VAV-cooling and the fin-tube water or electric
heating units allows the installation to match the requirements of any climate
zone. Where winter conditions prevail, more heating units can be installed to
meet heating needs. Where hot summer conditions prevail, additional VAV-cooling
units can be employed to match the cooling requirements.
To claim maximum energy efficiency and occupant
comfort, care should be taken during construction to seal all floor panels.
Additional care should be taken to seal all openings through the floor either
into the space or into the walls where plumbing or electrical equipment
penetrates the floor plenum. Regular inspection during construction will
minimize problems upon building completion and commissioning.
In recent years, the application for UFAD systems has
shifted from owner-occupied high-tech facilities to a more general variety of
building spaces aiming to achieve LEED certification. UFAD provides superior
comfort by supplying conditioned air where it is required near the occupant.
Additional occupant comfort can be achieved by installing small units in the
core of the building with individually adjustable dampers controlled by the
occupant. By conditioning only the occupied area and stratifying the upper zone
with air supplied form the low-pressure floor plenum saves energy. Additional
energy can be saved by employing a passive VAV-cooling and fin-tube heating
system on the perimeter.
For your next LEED project, take advantage of UFAD to
provide lower energy (EA c1), controllability of systems for thermal comfort
(IEQ c6), and thermal comfort (IEQ c7).
Please
direct questions toward Titus Communications (communications@titus-hvac.com) and/or
Titus' TU/UFAD Product Manager Derrick Smith (dsmith@titus-hvac.com).
No comments:
Post a Comment