Vertical throw for supply grilles is not usually required since grilles mounted in a ceiling are not a normal application. But it sometimes happens and diffusers can be set to throw vertically.
The method of obtaining throw data is as follows.
1. Determine the flow rate in CFM and the jet velocity from the published horizontal throw data pages.
2. Refer to the engineering section of the Titus catalog; page B24. Find the sections entitled Estimating Downward Vertical Projection.
3. Using the table below, find the vertical line representing your flow ate in CFM.
4. Follow the vertical line to the jet velocity curve that corresponds to core velocity listed in the published data.
5. Project a horizontal line from where the vertical flow rate line intersects the velocity curve to the column on the right hand side of the figure.
6. Select the appropriate temperature differential (delta T) column and read that vertical distance.
Example: Using the published data from the data page above, determine a vertical projection of a 36 x 18 grille supplied with 2500 cfm at a delta T of 20 degrees.The core velocity at the top of the data page for that grille size and volume is 600fpm.
Using the procedure described above and Figure 24, we can estimate vertical projection for a grille supplied with 2500cfm and a core velocity of 600 fpm to be nearly 12 feet with a 20 degree delta T.
Additionally, the table is also useful for comparing isothermal throw to differential throw when only the isothermal data is available, by simply reading across the vertical projection columns on the right.
For example, when an isothermal vertical throw of 25 feet is known, simply read across the column to determine a vertical throw of 15 feet for vertical throw when the delta T is 20 degrees.
Mark Costello - GRD Product Manager
Thursday, October 18, 2012
Q&A: I Need Performance For an Oversize Grille But I Can’t Find a Duct Area That Matches - How Do I Calculate Performance?
1. Divide the duct area by two or more until you finda comparable duct area, and then multiply the throw by 1.4, this is a common constant for the adjustment in total air mass that is used for extrapolating throw performance. This conversion factor is also used in all of the linear diffuser conversion charts.
2. A good rule of thumb on sound is to increase the sound data by 3 NC to obtain a cumulative value.
Mark Costello - GRD Product Manager
2. A good rule of thumb on sound is to increase the sound data by 3 NC to obtain a cumulative value.
Mark Costello - GRD Product Manager
Q&A: How Do I Calculate Performance Data For Grille Sizes That Are Not Published in a Catalog?
Most manufacturers have a selection software program that can help solve this problem.
The Titus selection software program TEAMS is available as a free download from the Titus website. TEAMS contains many grille sizes not published in the catalog, and allows the user to input air volume (CFM) in increments other than those published.
If software like TEAMS is not available, the following method should be used.
1. Determine the nominal duct area in square inches by multiplying the nominal length and width of the desired grille size in inches.
E.g. 64 x 10 = 640 square inches
2. Convert the duct area from square inches to square feet by dividing the total square inches by 144 and rounding to a 2-place decimal.
E.g. 640 square inches / 144 = 4.44 square feet
3. Locate a published grille size in the catalog for which the nominal duct size is approximately the same. The nominal duct area in square feet is the column directly to the right of the listed nominal duct sizes.
E.g. 4.44 square feet approximates to the 4.50 square feet shown for a 36 x 18 supply grille, and is less than is less than a difference of 2%. Duct leakage often accounts for more of a discrepancy than 2% in terms of performance.
4. Locate the nearest approximate desired volume listed for the approximated grille size.
E.g. A desired volume of 2300 CFM falls approximately midway between the listed volumes of 2110 and 2532, therefore the median throw and NC values between the values for 2110 and 2532 should be used.
The median value of NC 23 and 28 is 25 after rounding to an integer value.
The median values of the 0 degree deflection values 39-59-84 and 47-65-93, are 43-62-88.
Mark Costello - GRD Product Manager
The Titus selection software program TEAMS is available as a free download from the Titus website. TEAMS contains many grille sizes not published in the catalog, and allows the user to input air volume (CFM) in increments other than those published.If software like TEAMS is not available, the following method should be used.
1. Determine the nominal duct area in square inches by multiplying the nominal length and width of the desired grille size in inches.
E.g. 64 x 10 = 640 square inches
2. Convert the duct area from square inches to square feet by dividing the total square inches by 144 and rounding to a 2-place decimal.
E.g. 640 square inches / 144 = 4.44 square feet
3. Locate a published grille size in the catalog for which the nominal duct size is approximately the same. The nominal duct area in square feet is the column directly to the right of the listed nominal duct sizes.
E.g. 4.44 square feet approximates to the 4.50 square feet shown for a 36 x 18 supply grille, and is less than is less than a difference of 2%. Duct leakage often accounts for more of a discrepancy than 2% in terms of performance.
4. Locate the nearest approximate desired volume listed for the approximated grille size.
E.g. A desired volume of 2300 CFM falls approximately midway between the listed volumes of 2110 and 2532, therefore the median throw and NC values between the values for 2110 and 2532 should be used.
The median value of NC 23 and 28 is 25 after rounding to an integer value.
The median values of the 0 degree deflection values 39-59-84 and 47-65-93, are 43-62-88.
Mark Costello - GRD Product Manager
Tuesday, August 21, 2012
Q&A: Compare Series vs. Parallel Fan-Powered Terminal Units
There are two types of fan-powered
terminal units - series and parallel. Every manufacturer offers both types and
special variations such as low profile and quiet units. Although the type of
unit to use is often up to personal preference, there are distinct differences:
Series fan-powered terminals have
fans that must run throughout the occupied mode in order to deliver ventilation
air to the zone:
- These
units act as boosters for the air handler because their fans move the
air the rest of the way to the zone. This allows the air handler to run at
system pressure far lower than other types of terminal units require. The
typical system pressure supplying series fan boxes is 0.50 IN WG.
- Since
the fan runs continuously during occupied periods, they provide constant
air motion and more air changes than other types of terminal units.
- The
continuous operation of the fan results in relatively constant sound
levels, unlike other types of terminal units that vary air volumes and/or
cycle fans.
Parallel fan-powered terminals have
fans that only switch on during the heating mode to pull warm return air from
the ceiling plenum:
- Since
the unit fan is off during the cooling mode, the box acts like a single
duct VAV and simply varies airflow from the air handler to maintain room
temperature. Typical system pressures are between 1.00 and 1.50 IN WG.
- Some
engineers do not specify parallel fan units because the fan cycling is
often noticeable to occupants.
- Parallel
fan units must include a backdraft damper to prevent primary air from
leaking back through the blower into the ceiling plenum. Leakage around
the backdraft damper can be an issue and could be considerable when
downstream pressure requirements are greater.
An ASHRAE research project (RP-1292)
completed in 2007 was conducted to determine which type of fan-powered terminal
used the least energy from a whole building perspective. The report said that
either unit could be equally efficient when properly sized and applied. This
original report only included units with standard PSC fan motors. A subsequent
addendum to the report, paid for by a consortium of interested parties, took
the newer ECM technology into account in the same energy model. It gave more of
an advantage to the series fan units.
Randy Zimmerman - Chief Engineer
Monday, August 13, 2012
Q&A: What is End Reflection and How Will Discharge Sound Ratings for Terminal Units Change in 2012
There is an acoustical phenomenon known as end reflection
that is regularly encountered in HVAC systems. It occurs whenever air flowing
in a duct reaches an outlet and suddenly expands to fill a room. Although it
might not be obvious to the casual observer, sound doesn’t necessarily travel
in the same direction as airflow. The greater the degree of expansion, the more
sound is reflected away from the room.
An acoustician might say, “End reflection is the acoustic
energy in an acoustic test duct that is prevented from entering the test space
by the impedance mismatch created by the termination of the acoustic test
duct”. In layman’s terms, whenever a rapid air expansion occurs, some portion
of the sound energy generated by the supply device (i.e. terminal unit, fan
system, air handler, room fan coil, etc) travels upstream back towards the
source. This is end reflection.
All terminal unit manufacturers test their products in
accordance with ASHRAE Standard 130 ‘Methods of Testing Air Terminal Units’.
This standard provides testing procedures for both radiated and discharge
sound. End reflection has been known to affect discharge sound readings for many
years, so the standard was amended in 1994 to specify that discharge ducts in
discharge sound tests must terminate flush to the inside wall of the test
chamber. This was necessary because the further a discharge duct projects into
the test chamber, the more end reflection occurs, effectively lowering the
sound levels measured within the test chamber.
Test data measured in accordance with ASHRAE Standard 130 is
used to produce catalog data in accordance with AHRI Standard 880 ‘Standard for
Performance Rating of Air Terminals’. The latest version of this standard
(880-2011) went into effect on January 1, 2012. It requires that manufacturers
calculate the end reflection loss (ERL) and add it back to the rated discharge
sound power levels of terminal unit products. A formula based on ASHRAE
Research Project RP-1314 is used to calculate the ERL for the dimensions of the
discharge duct used during the sound test. Although the calculated ERL is most
accurately applied to 1/3 octave sound data, manufacturers may apply it to
existing full octave sound data through 2014.
Here’s how the ERL is calculated:
First determine De, the equivalent duct diameter
(ft). If the discharge duct is round, simply use the duct diameter. In the more
likely situation that the discharge duct is rectangular, the equivalent duct
diameter must be calculated as:
De = SQRT [(4 x A) / (144 x π)]
where:
A = cross sectional area of duct (in2)
So for a terminal unit with a 15 in by 12 in discharge duct:
De =
SQRT [(4 x 180) / (144 x π)]
= 1.26 ft2
Now
ERL = 10 log [1 + (0.7 x
Co/π x f x De)2]
where:
Co = Speed of sound in air (use 1128 fps)
f = Octave band center frequency (Hz)
De = Equivalent diameter of the duct (ft)
So the end reflection loss of a 15 in x 12 in discharge duct
is:
2nd Octave band (125 Hz) = 5 dB
3rd Octave band (250 Hz) = 2 dB
4th Octave band (500 Hz) = 1 dB
5th Octave band (1000 Hz) = 0 dB
6th Octave band (2000 Hz) = 0 dB
7th Octave band (4000 Hz) = 0 dB
Adding this to the existing discharge sound levels of a
fan-powered product would likely raise the NC level by 6 points. The smaller
the discharge duct is, the greater the correction will be. Since research has
shown that low frequency corrections tend to become overstated as duct sizes
get very small, the maximum correction is limited to 14 dB.
So what does all this mean?
It means that every manufacturer
will need to update all published terminal unit discharge sound performance
data and selection software to meet the latest standards. Discharge sound
levels will increase for all terminal units and smaller units will see the
largest increases. The effect on large units could be negligible.
Will the actual discharge be higher?
No. The product will
perform exactly as it did before, but now all of the sound energy will be
properly accounted for. It would be fair to say that under the previous
standard, discharge sound was in many cases being understated.
In order to change the certified performance listings
posted on the AHRI website, all participating manufactures were required to
resubmit all of their products to the program. It will probably be months
before all of the changes are complete and posted on their new website.
Although AHRI has agreed to publish a full page announcement in trade magazines
to explain why these changes are necessary, it has not yet been sent out for
membership approval.
Randy Zimmerman - Chief Engineer
Monday, July 16, 2012
Q&A: How Do You Size Parallel Fan Powered Terminal Units?
Parallel flow (variable volume) fan powered terminals are
selected based on their capacity to handle the primary airflow. The same rules
which apply to the selection of single duct terminals can be used, except that
water coils are not in the primary airstream path, and will not affect sound
levels. The pressure drop of the water coils, however, which are on the fan
inlet in Titus parallel fan units, must be added to the expected discharge
pressure at the fan flow rate when entering the fan curve tables.
The fan is selected based on the minimum airflow
requirements for the space or the heating load required. In most cases the fan
can be downsized from the cooling flow requirement considerably, reducing both
first cost and operating cost. The fan is selected from the fan curves. The
downstream static pressure of the secondary air may not be the same as the
primary air, however. If the secondary airflow requirements are less than the
primary air requirements, the static pressure will be reduced. The following
equation can be used to determine the static pressure at reduced airflows. (Do
not forget to add water coil pressure drops to the fan requirement).
To select a Titus parallel fan powered terminal, refer to
the published fan curves and primary air pressure drop curves, together with
the application and sound power data.
In the parallel flow
type of unit, when the primary air is ON, the fan is typically OFF, and vice
versa. As shown in the Figure 1, the primary air and the fan discharge air
follow parallel paths into a common plenum. Therefore both airflows will
encounter the same downstream resistance at a given flow rate.
Since the primary and secondary airflows come from two
different sources-and often at two different specified flow rates-the volume
vs. pressure relationship in each of these airflows must be checked to ensure
adequate flow rates under actual job conditions.
Example: Select a Model DTQP for a maximum of 1400 cfm of
primary air with 1.00” wg inlet static pressure. The fan airflow required is
1150 cfm. The downstream resistance offered by the duct and diffusers has been
determined to be 0.30” static pressure at 1150 cfm.
Primary Air: From the air inlet pressure table, a size 4
with a 12” inlet will handle 1400 cfm of primary air with a minimum static
pressure drop of 0.23” through the primary air section. But since the
downstream resistance is 0.30” at 1150 cfm:
The overall primary air static pressure drop is:
0.23”+ 0.44”= 0.67” sp
Since a 1.0” static pressure is available at the inlet, the
selection will work. The damper in the primary air section will do some
throttling to hold the maximum air flow to 1400 cfm.
Secondary Air (Fan): From the fan curves, a size 4, without
coils, terminal will handle 1150 cfm at 0.30” static pressure, with the proper
setting of the standard SCR speed control.
Trenton Yarbrough - Director of Engineering
Tuesday, July 10, 2012
Q&A: Why Are Filters for Terminal Units An Option?
Optional filters on fan-powered terminal units are 1” thick
disposable filters that are highly recommended if there is any chance that the
units will be operating during construction. Construction dust can easily ruin
both the motor and blower, if the units are operated without filters in place. Dust
tends to deposit unevenly on blower wheels resulting in loss of balance. Any
build-up of fine dust or lint on the exterior of a permanently-lubricated fan
motor can create a migration path and wick the oil out of the bearings.
These optional filters should later be removed and discarded
during the balancing and commissioning process. Operating units after construction
with filters in place is not recommended. Fan-powered units, like all terminal
units, are designed for zero maintenance. This is necessary because terminal
units, unlike air handlers, are typically located above finished ceilings in
tenant spaces. Accessing the units regularly to change filters can be nuisance
to tenants, time-consuming for maintenance personnel and can easily result in
ceiling damage.
If filtering of return air is desired, we recommend the
installation of filter grilles in the ceiling. This allows the building and the
building owner the benefits of less costly standard filter sizes; more filter
area for longer service intervals and quicker access for easier replacement.
Randy Zimmerman ~ Chief Engineer
Randy Zimmerman ~ Chief Engineer
Subscribe to:
Posts (Atom)




