ECM Retrofit - Things to Consider
As most
people in our industry are well aware – a newer fan motor technology can
provide huge energy savings and extended service life. There are many existing buildings
full of older permanent split capacitor (PSC) motors that typically last for
10-12 years in a series fan-powered unit. These motors are 20-60% efficient and
service life may suffer if operating at lower speeds. As soon as these motors
start showing an increasing pattern of failures, building owners who are aware
of electronically-commuted motors (ECMs) may express an interest in upgrading
to this newer technology. ECMs have a minimum efficiency of 80% and a service
life of 25-30 years. It is possible to attempt this type of retrofit, but there
are a few things to be aware of.
Were the unit models in question ever
available with ECM?
If a
particular unit model has been available with an ECM option, all the parts and
pieces should be readily available. Of course the most important part is the
motor itself and it must be programmed for a given blower cabinet. Although it
may be possible to assemble parts and pieces that will fit into an existing
unit, motor programming could be an issue if the unit was never developed for
an ECM option. Depending on the number of units involved, it may be cost
prohibitive to develop custom ECM programming for each cabinet size. One
possible solution would be to factory program the ECMs for constant torque
rather than pressure independent control. This could limit or eliminate the
need for any development work.
Will the existing electrical service
handle the ECM?
The ECM
replacement will likely be rated for a different horsepower and full load
current. Although the resulting operating current draw should be less than the
PSC motor it replaced, motor nameplate ratings may require upsizing the supply
circuit in order to provide the necessary electrical safety. Obviously, this
could greatly complicate the retrofit process and add a lot of cost.
Did you know that the UL/ETL listing will
be voided?
Any field
modifications to a UL/ETL-listed product that results in a change of electrical
characteristics such as current draw or motor horsepower will void the listing.
This is true even if factory parts are field installed by factory personnel.
Once a UL/ETL-labeled product leaves the factory, any changes that do not match
the data found on the unit label will void the listing. The only way to
reinstate the label would involve having a UL/ETL inspector visit the jobsite
and field label the units. This could be very costly but may be unnecessary if local
inspectors will not be involved in the retrofit process.
Have you considered the total amount
of parts that will be required?
ECM retrofit
doesn’t just mean replacing the motor. It generally means replacing the motor,
the speed control, and blower assembly. It will likely also require additional
components like power cables, communication cables, and a power filter. It
could even require changing internal options like line and/or motor fuses.
Have you considered the cost of field
labor required?
All of these
modifications will have a field labor cost. It could easily take an hour to
access each unit and swap out the various parts. It may take longer depending
on the accessibility of a given unit. In an occupied building this work may
need to be carried out at night or on weekends. Additional hours of electrician
time would be required for any modifications to the supply circuit.
In summary
Although the temptation to upgrade from PSC
motors to ECM is strong, remember that the process is not as simple as just changing
motors. It involves many more parts and could require electrical work too. That
doesn’t necessarily rule out the possibility on an ECM retrofit. Many building
owners have contacted their local Titus representative to investigate the
possibilities. ECM technology is quickly taking over this industry and it’s
important to understand exactly what a retrofit may entail so that you can
provide the right answers to your customers.
For information on this topic, please contact Randy Zimmerman at rzimmerman@titus-hvac.com or Titus Communications at communications
Thursday, May 9, 2019
Wednesday, March 27, 2019
Options for Surface Mounting Ceiling Diffusers
One of the more frequently asked questions we receive in application engineering is in regards to surface mounting Titus diffusers. When a ceiling grid is not present, surface mounting is specified and the installation questions arise. Linear diffusers are available with concealed mounting, square and rectangular diffusers with square or round inlets are not.
The most important thing to know about surface mounting is that it normally requires additional framing to which the units will be secured. We often receive calls for mounting instructions after the sheet rock has been installed which is too late to provide framing without removing the installed surface.
Framing requirements will vary from one job to the next, but there are some general guidelines and terminology we use.
Obviously installing screws in the face of a diffuser will work as it does for grilles but the duct return flanges behind diffuser edges are generally not available to provide a secure mounting base for screws. Also, many surface mount frames do not have a flat surface nor is there a screw hole fastening option available. Furthermore, screw fastening certainly does not enhance the aesthetics of the installed diffuser.
| The TRM mounting frame makes installation of grilles, diffusers and other ceiling components in plaster and sheetrock ceilings as simple as inserting them in a standard T-bar type ceiling |
All sheetrock is mounted to ceiling joists. Joists are usually parallel to each other and spaced at two to three feet apart depending on local building codes, and in most cases, the framing for the diffuser can be mounted to the top of, and perpendicular to the joists. Screws are then used to mount the back pan to the framing. Framing members should be centered on the diffuser location to allow sufficient clearance for the diffuser inlet and associated duct. Additional care must be taken so as to avoid any protrusions or features that will occupy the space necessary for the framing on the rear side of the diffuser. Framing should also be at a depth that will allow the diffuser to firmly seat against the sheet rock. Most diffuser back pan heights are less than the depth of the joist. The sheet rock or ceiling surface is installed into an opening provided for the diffuser.
The diffuser core should be removed prior to installation to allow for screws to be installed in the top of the back pan transition; this is the flat portion on the rear of the back pan. Screws are then used to secure the back pan to the framing. It is helpful to use washers to prevent the screw heads from being driven through the back pan if the framing is not flush to the rear of the pan. In most cases the screws can be placed in a manner to not be visible from the occupied space after the diffuser core or face is re-installed.
![]() |
| The illustration above shows how the TMS diffuser would be mounted in sheetrock |
As an alternative to the framing process, and one that we suggest if the ceiling surface has been installed without prior framing for the diffuser mounting, is to use our rapid mount frame. The TRM frame can be installed in the space between the joists following the installation of the ceiling.
The TRM replicates a standard ceiling grid module and a lay-in (type 3) frame diffuser. The diffuser can then be laid in the TRM frame. The TRM frame does add a border to the finished appearance of the diffuser, but also can be utilized as an access port to the space above the ceiling by simply pushing the diffuser up and out of the opening.
While the TRM does represent additional diffuser cost, the reduced labor requirement and flexibility of the installation sequence offers a distinct advantage.
The TRM is available in steel and aluminum and is ordered as a separate line item. Remember, when using the TRM frame, the (type 3) diffuser frame must be used instead of the (type 1) diffuser frame.
For information on this topic, please contact Mark Costello at mcostello@titus-hvac.com or Titus Communications at communications@titus-hvac.com.
Thursday, February 14, 2019
ASHRAE STANDARDS UPDATE
Titus has long been involved in ASHRAE, making contributions in the form of basic research and development as far back as the 1950’s. We still have a strong commitment to this organization and its activities. There are many Titus employees who serve on various ASHRAE committees in order to stay current on industry standards and trends as well as to have input on emerging technology. The purpose of this article is to keep you up to date with changes to several important ASHRAE standards.
Since its founding in 1894, ASHRAE has produced and maintained countless standards and guidelines related to the HVAC industry. In 2012, ASHRAE rebranded itself to expand its scope to become an international organization and to cover all aspects of the so-called ‘built environment’. Officially, these standards are updated every four years, but interim addendums are published and added as approved. Standards that cover emerging technology or critical topics such as the following are updated on a continual basis.
ASHRAE Standard 170-2017 ‘Ventilation of Health Care Facilities’
Standard 170 includes guidelines and minimum requirements to designers of health care facilities such as hospitals and clinics. The 2017 edition includes a number of important improvements to the 2013 standard:
- Adiabatic humidifiers will now be acceptable
- Lowered requirements for exam rooms for less critical uses
- Clarification concerning the prohibition of controls to change pressure relationships between any spaces – not only airborne infection isolation and protective environment rooms
- Reduced requirements for electroconvulsive therapy procedure rooms
- Reduction in requirements for laboratories under certain circumstances
- Increased requirements for high hazard exhaust systems
- New space temperature requirements in sterile processing departments to match other industry groups
- New and clearer definition for primary diffuser arrays in operating rooms
In addition, the new edition has also been reformatted into three sections to cover hospital spaces, outpatient spaces, and nursing home spaces in order to better align the standard with Facility Guideline Institute publications that are similarly formatted.
ASHRAE Standard 55-2017 ‘Thermal Environmental Conditions for Human Occupancy’
Standard 55 sets the minimum conditions for acceptable indoor thermal environments including temperature, thermal radiation, humidity, air speed in the design, operation, and commissioning of occupied spaces. The 2017 edition includes several changes to the 2013 standard:
- Provides three compliance methods for comfort – graphical, analytical, and elevated air speed methods
- Provides a separate method for determining acceptable thermal conditions in occupant-controlled naturally-conditioned spaces
- Now uses clear and enforceable language with more easily understood requirements
- Provides clarification regarding approaches to elevated air speed calculations
- Reduces Appendix A to a single method for operative temperature calculations
- Adds a new requirement for calculating changes to thermal comfort due to solar radiation
- Includes documentation requirements and a sample form for compliance
- Standard 55 has therefore been substantially improved with the intent of clarifying its requirements and providing a clearer path to compliance.
Anyone interested in learning more is encouraged to obtain the latest editions of each of these standards.
For information on this topic, please contact Randy Zimmerman at rzimmerman@titus-hvac.com or Titus Communications at communications
Subscribe to:
Posts (Atom)