Friday, April 20, 2012

Designing for Comfort per ASHRAE Standards 55 and 62.1

The goal of a room air distribution system is to provide thermal comfort and a healthy living environment for occupants in the space. ASHRAE Standard 55-2010 Thermal Environmental Conditions for Human Occupancy and ASHRAE Standard 62.1-2010 Ventilation for Acceptable Indoor Air Quality provide designers with the guidance to optimize health and comfort in building spaces. Many codes including LEED 2009 require compliance with these ASHRAE Standards. This article will outline the goals of these standards and illustrate how to comply with these requirements.

Dsplacement ventilation diffuser shown in the
Willard Elementary School in Concord, Massachusetts.

The occupied zone as defined by Standard 55-2010 reads: “the region normally occupied by people within a space, generally considered to be between the floor and 6 ft. level above the floor and more than 3.3 ft. from outside walls/ windows or fixed heating, ventilation, or air-conditioning equipment and 1 ft. from internal walls.” The space from the interior walls inward 1 ft. serves as a mixing zone where room air is entrained into the supply air jet and mixes to provide thermal comfort in the occupied space. When designing UnderFloor Air Distribution (UFAD) systems or Thermal Displacement Ventilation (TDV) systems, the occupied area around the outlets may be excluded to a boundary where the total air jet from the outlet contains velocities greater than 50 feet per minute (fpm). These areas may also be known as the “clear zone”, “adjacent zone”, or “near zone”.
Any design must also include an adequate supply of Ventilation Air to the breathing zone of the space. ASHRAE 62.1-2010 defines ventilation air as “that portion of supply air that is outdoor air plus any re-circulated air that has been treated for the purpose of maintaining acceptable indoor air quality”. The breathing zone is “the region within the occupied space between planes 3 and 72 inches above the floor…”. We will discuss additional requirements for ventilation air later in this article. The primary factors to be considered when determining conditions for thermal comfort in the occupied space are: 1) Temperature, 2) Air Velocity, 3) Humidity, 4) Clothing insulation, and 5) Activity level of the occupants. All of these factors are inter-connected when determining the general occupant comfort of a space. The ideal temperature in a space (operative temperature) is where the occupant will feel neutral to their surrounding neither feeling any heat loss to the space or heat gain from the space. While the range of acceptable operative temperature may vary depending on other conditions, ASHRAE 55 requires the “Allowable Vertical Air Temperature Difference-Between Head (67”) and Ankles (4”) is limited to 5.4 F (3.0 C)”. Ideal air velocity in the space can vary with other factors but in general the goal is to keep spatial velocities less than 50 fpm during the cooling mode and less than 30 fpm during the heating mode. For many years, Titus has recommended maintaining the relative humidity level in the space between 25-60%. ASHRAE 55 does not define a lower limit and requires the dew point temperature be less than 62.2 degrees (F). Another factor affecting comfort is the clothing insulation level of the occupant. In most office environments, occupants clo level is between 0.5 and 1.1, where 0.5 would be a person wearing no socks, sandals, short sleeve shirt or blouse, and shorts or skirt. The 1.1 clo level would include long pants, socks, long sleeve shirt and dress coat or sweater. The range of operative temperature where both a 0.5 and 1.1 occupants are in the same space is very narrow. The final item of consideration for design comfort is the intended activity level of the occupant in the space. In most office environments the metabolic (met. Rate) is between 1.0 and 1.3. This includes occupants who are sedentary to casual movement about the space.
The three common methods of room air distribution used in commercial buildings in the United States are fully mixed, (e.g. overhead distribution); fully stratified (e.g. displacement ventilation); and partially mixed, (e.g. most underfloor air distribution systems). Since interior zones usually have adequate heat loads from occupants and equipment and few heat losses, the discussion for interior spaces will be cooling only. For the perimeter spaces, discussion will be how to meet the requirements for heating and cooling from the same overhead outlet. Design methods for cooling an interior zone and heating a perimeter zone vary with each method.
For fully mixed systems, the pattern of the air delivered to the space must be considered when selecting an air outlet. Ceiling diffusers typically exhibit flow in a circular (radial) or cross flow (directional) discharge air pattern. The circular pattern usually provides shorter throw, higher mixing and tends to maintain ceiling effect to low velocity before turning back on itself. This pattern is ideal for variable air volume (VAV) cooling by providing less drop and more uniform temperatures in the space. The cross flow (directional) air pattern has longer throw but with less induction may lose ceiling effect creating drafts in the occupied zone. Plenum slot diffusers typically discharge air in a directional air pattern but some are available with “spreaders” to produce a more radial discharge air pattern. Sidewall grilles equipped with vertical deflectors can be adjusted from zero degree (directional pattern) to 45 degree spread (radial pattern). So, regardless of the desired type of outlet, the air pattern can be either radial or directional to best meet the comfort requirements of the space. Proper selection for comfort can be insured by using the ADPI selection program in TEAMS.

The Titus DynaFuser installed in the
Virginia Tech Solarhouse.

Typically for perimeter applications where the same outlet is being used for both heating and cooling, a linear slot diffuser or plenum slot diffuser is employed. When a fixed air pattern diffuser is used, it is typical to supply half of the air across the ceiling for cooling and half down the glass for heating. For perimeter heating, the requirements for table 6-2 of ASHRAE Standard 62.1-2010 must be considered. The intent of table 6-2 is to insure that the ventilation air supplied to the space be delivered to the breathing zone as well. For ceiling supply of warm air with a ceiling return, the requirements for heated air are to reach a terminal air velocity of 150 feet per minute (fpm) to within 4.5 ft. of the floor. To a terminal velocity of 150 fpm or more, air is temperature independent which means the distance air will travel will be the same for isothermal air (catalog values), warm air and cool air. This means that during heating, ventilation air will be pushed down into the breathing zone with enough heat energy to meet Standard 55’s requirement for a temperature gradient of less than 5.4 degrees. In addition, the differential temperature between warm supply air and space temperature with a ceiling return must be 15 degrees or less. Thus the maximum supply air temperature for a 75 degree room would be 90 degrees. When the heating supply air temperature exceeds the 15 degree limit, the ventilation air volume for heating must be increased by 25%.
Choosing an auto-changeover diffuser like Dynafuser or EOS does not change the Standard 62.1 requirements, but will lower energy cost and improve comfort in the space. Delivering all the warm air down the glass during heating will save energy. With a fixed pattern diffuser, half of the warm air will be discharged across the ceiling and with a ceiling return can be short circuited without reaching the occupied space level. Additionally, higher comfort will be realized in the space as the heated air can be designed to deliver warm air all the way to the floor. Comfort may be increased during cooling as well as the cool air will be projected across the ceiling eliminating the potential for drafts from the jet projected down the glass with a fixed pattern diffuser.
For partially mixed air distribution systems (typically UFAD), the core area usually experiences even loading throughout the occupied area. The goal of partially mixed systems is to save energy by comfort conditioning the lower occupied level in the space and allowing the upper level of the space to stratify. Occupant comfort is achieved by delivering cool conditioned air from the plenum under the floor through swirl diffusers or rectangular shaped outlets near the occupants work area. Individuals can enhance their personal comfort by adjusting the damper at the outlet near their workspace. For common areas such as hallways and break rooms, outlets can be equipped with actuators that are controlled by a common thermostat located in the space.

UFAD Perimeter System installed in the Visteon
Village project in Van Buren Township, Michigan.

Perimeter zones for partially mixed systems create a greater challenge as the loads are dynamically changing due to outdoor solar and air temperature changes. A common method for perimeter zone control is locating a low profile fan powered terminal unit under the floor near the perimeter supplying air to linear bar grilles. The fan powered terminal can be equipped with an electric or hydronic coil. Cool plenum air can be supplied to the outlets when cooling is required and the coil can be employed to warm the air as required during heating conditions. The design challenge is selecting outlets that will limit the throw of the air pattern so that air will not bounce off the ceiling and create drafts in the adjacent occupied area.
Energy to operate the fan terminals can be eliminated and higher comfort can be achieved on the perimeter by using the TAF-L perimeter distribution outlets. With a 6” wide custom design TAF-L bar grille located along the perimeter of the space, the modular 4’ long TAF-L-V (cooling), can be attached to provide up to 225 cfm (at 0.07” plenum pressure) per 4’ unit of cooling. The TAF-L-V damper is controlled by a space thermostat to provide cooling as required. The special arrangement of bars in the grille is designed to limit the throw from the outlet during cooling. The 4’ long TAF-L-W or TAF-L-E heating module can be attached to the TAF-L grille to supply up to 3000 Btu heat to the perimeter. The heating units operate by combining the cool convection currents from the glass with the warm currents on the floor. The mixture is induced through the heat exchanger with warm air being discharged through the grille and up the glass. Space temperature is controlled by a room thermostat controlling the water flow or electric current flow to the electric heating element. The modular design allows the system to be custom designed for use in multiple climate regions.
Fully stratified design (typically TDV), conditions a space by discharging cool supply air through an outlet located at floor level near or in a wall or may be centrally located in the open space. Low velocity air (< 80 fpm) is discharged horizontally across the floor. Air moves with little mixing across the floor until it contacts a heat source such as an occupant or piece of warm equipment in the space. Cool air will mix with the radiant heat from the source and stratify toward the ceiling. The return is usually located at or near the ceiling. The area between the outlet and where the air speed reaches 40 fpm is the “clear zone” and should not be included in the occupied area. Titus provides units with adjustable air patterns so the clear zone can be controlled to meet project requirements for space occupancy. ASHRAE Standard 62.1 table 6-2 provides a 20% bonus for TDV systems. This means that ventilation air can be reduced by 20% or the 20% can be used toward the 30% required for an additional LEED IEQ credit 2.
While TDV systems typically require a separate system for heating, Titus has introduced the Plexicon heating/cooling diffuser. A standard rectangular outlet is located near or mounted in a wall discharging cool air from the upper chamber. When heating is required, an internal baffle is moved to change the flow of air from the upper chamber to the lower chamber where it flows through a linear bar grille to satisfy heating requirements.
Regardless of which type of system you are using on your project, studies have shown that occupants who are comfortable are more productive. Designing for comfort, keeps paying back dividends forever.
Jim Aswegan - Chief Engineer

Friday, February 17, 2012

What is the Adjacent Zone?

ASHRAE Standards 55 and 62.1 summarizes ASHRAE’s standards for thermal comfort and minimum ventilation and explains how to apply air outlets to comply with each of these standards. Even though the article also references the definition of the ‘adjacent zone’ that exists in close proximity to Thermal Displacement Ventilation (TDV) diffusers, it’s also important to understand how displacement ventilation products can differ with respect to occupant comfort.

To briefly recap, displacement diffusers used in fully-stratified systems deliver low velocity cooling directly to the occupied zone. Since the supply air is cooler than the room air, it cascades down the face of the diffuser and travels across the floor in a thin layer generally no more than 4 inches deep.

Adjacent Zone

The ‘adjacent zone’ is defined as any portion of the room where discharge velocities exceed 40 fpm. This area is not recommended for stationary occupants who would likely feel a chill around their ankles.

Although displacement ventilation diffusers are available from most manufacturers in a myriad of shapes and sizes, there are really two basic types of designs being manufactured:

• Fixed Air Pattern
• Adjustable Air Pattern

Although all displacement diffusers include a perforated face plate and a rear supply plenum, fixed air pattern diffusers are characterized by a perforated central baffle. The purpose of the central baffle is to further slow and spread the supply air evenly over the face plate. Diffusers of this design are less costly to produce but they must be selected very carefully to ensure that the symmetrical adjacent zones they create will not result in thermal discomfort for stationary occupants.

Fixed air pattern diffusers also lack versatility in situations where spaces are being reconfigured or re-purposed. Rather than used a fixed perforated central baffle, adjustable air pattern diffusers include a baffle fitted with air pattern controllers. These sturdy steel pattern controllers are easy to remove and reset and do not raise concerns about plastic materials in the air stream. Although these pattern controllers ship out of the factory in a default arrangement to create a standard symmetrical discharge pattern, they provide adjustability for enhanced versatility and improved occupant comfort.


Left: Fixed air pattern displacement diffusers in standard operation. Right: Adjustable air pattern controllers allow for adjustability of the adjacent zone for maximum occupant comfort.


 Rather than settle for a fixed discharge pattern, Titus displacement ventilation products can be easily adjusted to direct air away from occupants and areas that may result in comfort issues (now or in the future). Titus displacement ventilation products include adjustable pattern controllers so that you can control your ‘adjacent zone’.


Randy Zimmerman – Titus Chief Engineer



Thursday, February 9, 2012

RP-1335 Test Effects of Diffuser Performance

ASHRAE Study 1335 on the effects of typical inlet conditions on ceiling diffusers and their performance began in 2009 at the University of Nevada, Las Vegas (UNLV) laboratories.

The goal of this ASHRAE study was to test and determine the impact on manufactures catalog performance data for ceiling diffusers created by typical field-installed inlet conditions.

ASHRAE Standard 70-2006, is the current “Method of Testing the Performance of Air Outlets and Air Inlets” used by manufactures to obtain catalog performance data. Standard 70 requires diffusers to be tested with a minimum of 3 diameter equivalents of straight duct ahead of the inlet with even flow throughout the duct. 

So the question is, “What happens when diffusers are mounted in buildings and how much variation in performance will we see with typical field installed conditions?”

When building air distribution systems, designers and system installers require accurate quantitative information on how the installed system will perform to achieve optimum efficiency and comfort, and they rely on performance data from manufactures catalogs. But catalog performance reflects perfect inlet conditions. If field installations adjustments are required to the manufactures data due to typical field installation procedures, the extent of these adjustments to the performance data of throw, pressure loss, and sound will be shown in the results of this study.

This study incorporated the performance data of multiple installations using six different types of typical ceiling diffusers. The data in this report compares the performance results of these various field installations to the performance data collected per ASHRAE 70-2006. All diffusers were first tested per ASHRAE 70-2006 to determine the base performance data and then various modifications to the installation were conducted.

Full scale testing was done in the UNLV laboratory with diffusers mounted in various inlet conditions over a large range of flow rates with various duct approach angles, as well as:
  • hard duct vs. flex duct
  • various straight duct heights above the diffuser
  • using an elbow attached to flexible duct
  • close coupling duct installations
In addition, the effect of various dampers connected directly to the diffusers with multiple inlet conditions was also studied.

SIGNIFICANT RESULTS SHOW

DUCT CONNECTIONS

Installations with flexible duct connections and tight bends affect diffuser performance significantly due to uneven air flow through the diffusers.

THROW

The throw from the diffuser is affected with elbows directly attached to the diffuser inlets. The throw from the a diffuser with an 90-degree elbow directly attached to diffusers of all types tested showed an average throw increase in the (forward) direction and a decrease in the (backward) direction. Dampers, depending upon the design, can reduce this asymmetry problem a significant amount. These dampers, however, also add a significant sound increase.

PRESSURE LOSS

The data shows that a flexible duct elbow to a diffuser as compared to an all metal elbow has a greater pressure loss. This data also shows that the higher the pressure loss of the diffuser, the less the effect of inlet conditions and damper conditions. The average pressure loss increase due to dampers on the face of diffusers is about 50%. This data shows that dampers directly mounted on the diffuser inlet should be avoided.

SOUND

A very interesting group of information deals with the amount of straight duct required after an elbow to obtain the same performance data as shown in manufactures catalogs.  This data shows that three diameters of straight duct down-stream from the elbow typically resulted in the same sound levels as cataloged and tested by ASHRAE 70-2006. However, elbows directly connected to diffusers typically increase the NC. Dampers also contribute to sound increases. Dampers in the full open condition can add to NC levels. Flex duct elbows averaged higher than rigid duct. The sound data from plaque diffusers was interesting. This data showed that with a fixed diffuser face free area as we have with plaque diffusers, that the increase in sound is not as critical as compared to diffusers of this type with inlets having a greater free area than the diffuser face.       

CLOSE COUPLING OF DIFFUSERS
Close coupling is when diffusers are connected directly below a ducting system. The length of duct between the supply duct and the diffuser was studied. The results were very similar to those seen with elbows to diffusers. Another variable was also seen which deals with the main duct velocity and the pressure loss of the diffuser as related to the velocity pressure in the main supply duct. In general, as the main duct velocity increased greater than the diffuser inlet velocity, the sound from the diffuser increased. Once again, open dampers also increased the sound.

DAMPERS

In general, the data show that dampers should be mounted as far up stream form the diffusers as possible. Dampers directly mounted on diffusers cause high velocity air streams on the diffuser cones and can cause significant sound increases.

RESOLUTION

As part of the report, a set of tables were developed to easily predict how various installation configurations will affect diffuser performance. A set of three reports were given at the Winter ASHRAE 2012 meetings in Chicago, and copies of this data are now available through ASHRAE.

Leon Kloostra - Titus Senior Chief Engineer

Friday, December 16, 2011

Q&A: Can you tell me more about curving?

We recomend a custom submittal drawing be used for curved diffusers when you have a custom curving need.  The submittal files are used both by a curving vendor and at receiving plants to ensure accuracy.
Custom curving requires that the customer specify the border style, direction of curve (whether plan - ceiling or floor installs or face curves - arches), radius and length.
Custom curving is best performed using precision stretch-forming techniques developed for the aeronautical industry.  They are generally more accurate and faster than roll-forming techniques.
How Exactly Does s Stretch Forming Work?

Stretch forming allows material to be formed along a custom template while eliminating wrinkling along the inside edges of the curve.

Aluminum is the most commonly used, but other metals can be stretch formed. Stretch forming is a process that permanently bends metal into a desired shape using heat to treat it then press it over a die while the metal is held at a tension beyond the yield point.

When the metal is held just beyond the yield point it will permanently retain the desired contour and shape. Some materials may require multiple stretching operations to permanently alter the memory of the metal.
A. Both ends of the work material are inserted in gripper jaws that are mounted on a swing-arm.
B. The material is then stretched outward to its yield point.
C. Then wrapped around the form die while maintaining the stretch force.
D. When the metal has taken shape, the force is released and the finished curved product is removed. The material’s memory has been permanently altered to the desired shape.




Mark Costello - GRD Application Engineering Manager

Tuesday, November 22, 2011

Active Chilled Beam Design - Occupant Comfort

Active chilled beam systems offer design consultants an effective means to create a comfortable space while offering numerous opportunities for energy savings. There are several critical aspects of the design that must be addressed to ensure occupant comfort in addition to meeting the load requirements in the space. These include primary airflow supplied to the beams, placement and sizing of the beams.

The first tem that should be addressed in design of a chilled beam system is the volume of primary air supplied to the space. In chilled beam systems the primary air is the only source for both ventilation air and removal of latent heat gains in the space.

In order to determine the primary air requirements for the space in an active beam system, two separate items need to be considered. The minimum ventilation rate for the space must be compared to the amount of conditioned air required to maintain control of the humidity level in the space. Guidelines for determining the minimum ventilation requirements are given in ASHRAE standard 62.1-2010. The required flow ate to meet the latent load is determined by the following equation:


It follows that the required flow ate to maintain control of the humidity will rapidly increase as the difference between the room air and primary air humidity ratios decrease. As a result, designs seeking to maintain relatively low humidity ratios will need a high primary flow ate if the dew point temperature of the supply air is close to the design dew point in the room. Criteria for maximum dew point temperature in the space is set in ASHRAE Standard 55-2010; for a room design temperature of 75BF the maximum relative humidity is 63.5%. The larger of the two flow rates calculated will dictate the requirements in the space.

Once the required supply flow ate has been determined the beam throw pattern and unit size can be selected.

While there are many factors affecting the size/length of the chilled beam, the appropriate throw pattern should be determined based on multiple room considerations, e.g., shape/layout, intended use of the space, and windows.

In open office spaces as well as internal offices two-way or four-way beams are typically used. The flexibility provided by two-way and four-way beams, due to multiple sizes and nozzle configurations, allow them to be appropriately applied in most applications. One-way beams are typically used in perimeter zones and small spaces such as individual offices and hotel rooms.

After the throw pattern has been decided, placement of the beam within the space can be determined. Active chilled beams, because of their design, share throw characteristics with conventional slot diffusers. Placement and orientation of active beams is critical for thermal comfort due to long throw values associated with active beams.


In open office plans t is typically more cost effective to use several longer beams that are installed parallel in space, instead of numerous smaller beams the length of the module division. However in an open office the number and size of beams used will be determined by balancing the cost per beam, cost of air side operating pressure, and water side pumping power to achieve optimum energy efficiency. When applying two-way and four-way beams in small offices and individual offices the recommended location is directly above the occupants. This will result in the lowest velocities within the occupied space. It is also recommended that two-way beams are installed lengthwise in the space. This will allow for the use of longer beams, reducing the cooling requirements per linear foot which will in-turn lower total air flow per foot and the resulting velocities in the space ensuring occupancy comfort. If placement is required near a wall use of one-way throw beams are recommended. One-way beams can also be effectively used in perimeter zones for cooling applications; however they should be supplemented with baseboard heating to address window loads during the heating season. Two-way beams can be effectively applied in perimeter zones for both heating and cooling. Care must be taken if two-way beams are installed parallel to windows. In intermediate seasons when internal cooling is required and window surfaces are cool an acceleration of the air can occur in the space creating drafts and potential discomfort.

Once the primary air requirements, type, and orientation of the active beams in the system have been determined an iterative approach should be used to determine unit size/length and final placement of the beam based on operating conditions. In addition to providing latent cooling, supply air will deliver sensible cooling. Location for final placement should take into consideration the allowable average air speed in the occupied space in accordance with ASHRAE Standard 55-2010. Accounting for the air side sensible capacity will allow for reduced capacity requirements of the water coils in the beams.




Designing with this in mind will reduce airflow requirements per linear foot, which will help to meet the requirements for thermal comfort. When placing two beams in the same space as shown in Figure 2, care must be taken to ensure that the colliding air streams do not result in velocities over 50 fpm causing discomfort. A general guideline to achieve air velocities of 50 fpm or less in the occupied space is to ensure the velocities of colliding (V collisions) airstreams are below 100 fpm. If velocities at the point of collision are greater than 100 fpm, the distance from the ceiling for the airflow to slow to 50 pm is noted in the equation below:

Buildings and systems utilizing active chilled beams can achieve significant reduction in energy usage through optimization of the active beams selected, and the equipment selected for providing primary air and chilled water to the units. While savings may be obtained through reduced energy usage, the cost of reduced productivity resulting from worker discomfort can quickly erode the realized energy savings. Therefore it is critical that the appropriate considerations must be made to ensure thermal comfort is maintained in the space.



Matt McLaurin - Senior Design Engineer

Application: Options for Surface Mounting Ceiling Diffusers

One of the more frequently asked questions we receive in application engineering is in regards to surface mounting Titus diffusers. When a ceiling grid is not present, surface mounting is specified and the installation questions arise. Linear diffusers are available with concealed mounting, square and rectangular diffusers with square or round inlets are not.

The most important thing to know about surface mounting is that it normally requires additional framing to which the units will be secured. We often receive calls for mounting instructions after the sheet rock has been installed which is too late to provide framing without removing the installed surface.

Framing requirements will vary from one job to the next, but there are some general guidelines and terminology we use.

Obviously installing screws in the face of a diffuser will work as it does for grilles but the duct return flanges behind diffuser edges are generally not available to provide a secure mounting base for screws. Also, many surface mount frames do not have a flat surface nor is there a screw hole fastening option available. Furthermore, screw fastening certainly does not enhance the aesthetics of the installed diffuser.

All sheet rock is mounted to ceiling joists. Joists are usually parallel to each other and spaced at two to three feet apart depending on local building codes, and in most cases, the framing for the diffuser can be mounted to the top of, and perpendicular to the joists. Screws are then used to mount the back pan to the framing. Framing members should be centered on the diffuser location to allow sufficient clearance for the diffuser inlet and associated duct. Additional care must be taken so as to avoid any protrusions or features that will occupy the space necessary for the framing on the rear side of the diffuser. Framing should also be at a depth that will allow the diffuser to firmly seat against the sheet rock. Most diffuser back pan heights are less than the depth of the joist. The sheet rock or ceiling surface is installed into an opening provided for the diffuser.
The diffuser core should be removed prior to installation to allow for screws to be installed in the top of the back pan transition; this is the flat portion on the rear of the back pan. Screws are then used to secure the back pan to the framing. It is helpful to use washers to prevent the screw heads from being driven through the back pan if the framing is not flush to the ear of the pan. In most cases the screws can be placed in a manner to not be visible from the occupied space after the diffuser core or face is re-installed.



As an alternative to the framing process, and one that we suggest if the ceiling surface has been installed without prior framing for the diffuser mounting, is to use our rapid mount frame. The TRM frame can be installed in the space between the joists following the installation of the ceiling.


The TRM replicates a standard ceiling grid module and a lay-in (type 3) frame diffuser. The diffuser can then be laid in the TRM frame. The TRM frame does add a border to the finished appearance of the diffuser, but also can be utilized as an access port to the space above the ceiling by simply pushing the diffuser up and out of the opening.


While the TRM does represent additional diffuser cost, the reduced labor requirement and flexibility of the installation sequence offers a distinct advantage.


The TRM is available in steel and aluminum and is ordered as a separate line item. Remember, when using the TRM frame, the (type 3) diffuser frame must be used instead of the (type 1) diffuser frame.




Mark Costello - GRD Application Engineering Manager